Temperature Controllers www.tempco.com | (800) 323-6859 | email: [email protected] 13-41 Power Input Standard: 90-264 VAC, 47-63 Hz, 15 VA, 7W maximum Optional: 11-26 VAC / VDC, 15 VA, 7W maximum Signal Input Input 1 Resolution: 18 bits Sampling Rate: 5 samples / second Accuracy: ±.24% of span typical Maximum Rating: -2 VDC minimum, 12 VDC maximum (1 minute for mA input) Temperature Effect: ±1.5 μV / °C for all inputs except mA input ±3.0 μV / °C for mA input Sensor Lead Resistance Effect: T/C: 0.2μV/ohm 3-wire RTD: 2.6°C/ohm of resistance difference of two leads Burn-out Current: 200nA Common Mode Rejection Ratio (CMRR): 120 dB Normal Mode Rejection Ratio (NMRR): 55 dB Sensor Break Detection: Sensor open for TC, RTD and mV inputs; sensor short for RTD input; below 1 mA for 4-20 mA input; below 0.25V for 1-5V input; unavailable for other inputs Sensor Break Response Time: Within 4 seconds for TC, RTD and mV inputs; 0.1 second for 4-20 mA and 1-5 V inputs Input 2 Resolution: 18 bits Sampling Rate: 1.66 times per second Sensor Break Response Time: 0.5 second Types: Current Transducer: 0 to 50 Amp mA: -3 to 27 mA V: -1.3 to 11.5 VDC Input 3 Event Input Functions: Select 2nd setpoint, and/or PID, disable output 1 and/or output 2, remote lockout, reset alarm 1 and/or alarm 2 Output 1 or Output 2 Relay Rating: 240 VAC, 2 Amp Pulsed Voltage: Source voltage 5V, Current limiting resistance 66Ω Linear Output — Characteristics Type Tolerance Zero Tolerance Span Capacity Load 4-20 mA 3.6-4.0 mA 20-21 mA 500Ω max 0-20 mA 0 mA 20-21 mA 500Ω max 0-5 VDC 0 VDC 5-5.25 VDC 10 KΩ min 1-5 VDC 0.9-1.0 VDC 5-5.25 VDC 10 KΩ min 0-10 VDC 0 VDC 10-10.5 VDC 10 KΩ min Resolution: 15 bit analog to digital converter Isolation Breakdown Voltage: 1000 VAC Solid State Relay (Triac) Output Rating: 1A / 240 VAC Inrush Current: 20A for 1 cycle Min. Load Current: 50 mA rms Max. Off-state Leakage: 3 mA rms Max. On-state Voltage: 1.5 VAC rms Insulation Resistance: 1000 Megohms minimum at 500 VDC Dielectric Strength: 2500 VAC for 1 minute Alarm 1 / Alarm 2 Relay: 2 Amp, 240 VAC Alarm 1: SPDT Alarm 2: SPST (NO) Alarm Functions: Dwell timer PV1-PV2 High / Low Alarm Deviation Band High / Low Alarm Loop Break Alarm PV2 High / Low Alarm Sensor Break Alarm Alarm Mode: Normal, Latching, Hold, Latching / Hold Dwell Timer: 0 - 6553.5 minutes Data Communications Interface: RS-232 (1 unit), RS-485 (up to 247 units) Protocol: Modbus Protocol – RTU mode User lnterface Dual 4-digit LED Display: 0.40" (10 mm) Red Process Display Keypad: 3 keys 0.31" (8 mm) Green Setpoint Display Programming Port: For automatic setup, calibration and testing Control Mode Output 1: Reverse (heating) or direct (cooling) action Output 2: PID cooling control, cooling P band 1 - 255% of PB On-Off: 0.1 - 100.0°F hysteresis control (P band = 0) P or PD: 0 - 100.0% offset adjustment PID: Fuzzy logic modified Proportional band: 0.1 - 900°F (500°C) Integral: 0 - 1000 seconds Derivative: 0 - 360 seconds Cycle Time: 0.1 - 100 seconds Manual Control: Heat (MV1) and Cool (MV2) Auto-tuning: Cold start and warm start Failure Mode: Auto-transfer to manual mode with sensor break or A-D converter damage Ramping Control: 0 - 900°F/min or 0 - 900°F/hr ramp rate Power Limit: 0 - 100% for output 1 and output 2 Remote Setpoint: Programmable range for voltage or current input Digital Filter: Time constant: settable from 0.2 to 60 seconds Analog Retransmission Analog Retransmission Functions: PV1, PV2, PV1-PV2, PV2-PV1, Setpoint, MV1, MV2, PV-SV deviation value Output Signal: 4-20 / 0-20 mA, 0-1, 0-5, 1-5, 0-10 VDC Accuracy : ±0.05 % of span, ±0.0025 %/°C Environmental and Physical Operating Temperature: 14 to 122°F (-10 to 50°C) Storage Temperature: -40 to 140°F (-40 to 60°C) Humidity: 0 to 90% RH, non-condensing Dielectric Strength: 2000 VAC, 50/60 Hz for 1 minute Dimensions: 3-3/4 × 1-7/8 × 3-1/8" (96 × 48 × 80 mm) H×W×D Depth behind panel: 2-9/16" (65 mm) Panel Cutout: 3-5/8" × 1-25/32" (92 × 45 mm) H×W Weight: 0.49 lb. (220 grams) Approval Standards Safety: UL873, EN61010-1 (IEC1010-1) Protective Class: IP 20 housing & terminals with protective covers EMC: EN61326 Stock and Common Part Numbers (Power Input: 90-264 VAC, no Alarm 2, no data com) Part Signal Number Input Out 1 Out 2 Alarm 1 TEC33001 tc relay none relay TEC33002 tc relay relay none TEC33003 tc relay relay relay TEC33004 tc 4-20 mA none none TEC33005 tc 4-20 mA none relay TEC33006 tc DC pulse none none TEC33007 tc DC pulse none relay Rear Terminal Connections