Temperature Controllers www.tempco.com | (800) 323-6859 | email: [email protected] 13-17 Power Input Standard: 90-250 VAC, 47-63 Hz, 8VA, 4W maximum Optional: 11-40 VDC / 20-8 VAC, 47-63 Hz, 8VA, 4W maximum Signal Input Resolution: 18 Bits Sampling Rate: 5 Times / Second (200msec) Maximum Rating: -2VDC minimum, 12VDC maximum Sensor Break Detection: Sensor open for thermocouple and RTD inputs, sensor short for RTD input, below 1mA for 4-20mA input, below 0.25V for 1-5V input, not available for other inputs Sensor break responding time: Within 4 seconds for thermocouple and RTD inputs, 0.1 second for 4-20mA and 1-5V inputs Event Input Number of Event Inputs: 1 Logic Low: -10V minimum, 0.8V maximum Logic High: 2V minimum, 10V maximum CT Input CT type: TEC99998 Accuracy: ±2% of full scale reading, ± 1 digit maximum Input Impedance: 294Ω Measurement Range: 0-50A AC Output of CT: 0-5V DC CT Mounting: Wall (Screw) mount Sampling Rate: 1 time/second Output 1 /Output 2 Type: Relay, pulsed voltage, linear voltage and linear current Relay Rating: 2A, 240V AC, 200000 life cycles for resistive load Pulsed Voltage: Source voltage 5V, Current limiting resistance 66Ω Linear Output Resolution: 15 Bits Isolation Breakdown Voltage: 1000 V AC Load Capacity of Linear Output: Linear current: 500Ω maximum, Linear voltage: 10KΩ minimum Alarm Relay Type: Form A Maximum Rating: 2A, 240VAC, 200000 life cycles for resistive load Alarm Functions: Dwell timer, Deviation low, Deviation high, Deviation band low, Deviation band high, Process high, Process low Alarm Mode: Latching, Hold, Normal, Latching/Hold Dwell Timer: 0.1-4553.6 minutes Data Communications Interface: RS-485 Protocol: Modbus RTU Address: 1-247 Baud Rate: 2.8 - 115.2 Kbits/sec Parity Bit: None, Even or Odd Stop Bit: 1 or 2 Bits Data Length: 7 or 8 Bits Communication Buffer: 160 bytes Analog Retransmission Output Signal: 4-20 mA, 0-20 mA, 0-10V Resolution: 15 Bits Accuracy: ±0.05% of span ± 0.0025% / °C Load Resistance: 0-500Ω for current output, 10KΩ minimum for voltage output Isolation Breakdown: 1000VAC minimum Linear Output Ranges: 0-22.2mA (0-20mA / 4-20mA), 0-5.55V (0-5V, 1-5V), 0-11.1V (0-10V) User Interface Keypad: 4 Keys Display Type: 4 digit LCD display No. of Display: 2 Upper Display Size: 0.31" (8mm) Lower Display Size: 0.25" (6.5mm) Programming Port Interface: Micro USB PC Communication Function: Automatic Setup, Calibration and Firmware Upgrade Control Mode Output 1: Reverse (Heating) or Direct (Cooling) Action Output 2: PID cooling control, Cooling P band 50~300% of PB, Dead band -36.0 ~ 36.0 % of PB ON-OFF: 0.1-90.0 (°F) hysteresis control (P band = 0) P or PD: 0-100.0 % offset adjustment PID: Fuzzy logic modified Proportional band 0.1 ~ 900.0°F, Integral time 0–3600 seconds, Derivative time 0-360.0 seconds Cycle Time: 0.1-90.0 seconds Manual Control: Heat (MV1) and Cool (MV2) Failure Mode: Auto transfer to manual mode while sensor break or A-D Converter damage Ramping Control: 0 to 900.0°F / Minute or 0 to 900.0°F / Hour Ramp Rate Environmental and Physical Specifications Operating Temperature: -10°C to 50°C Storage Temperature: -40°C to 60°C Humidity: 0 to 90 % RH (Non-Condensing) Insulation Resistance: 20MΩ minimum (@500V DC) Dielectric Strength: 2000V AC, 50/60 Hz for 1 Minute Vibration Resistance: 10 to 55 Hz, 10m/s2 for 2 Hours Shock Resistance: 200 m / s2 (20g) Moldings: Flame retardant polycarbonate Mounting: DIN Rail, 35 mm Dimensions H × W × D: 3-3/4 × 7/8 × 3-1/4" (96 × 22.5 × 83 mm) Depth Behind Panel (mm): n/a Cut Out Dimensions (mm): n/a Weight: 6 oz (160 g) IP50 for the front panel, IP20 for rear terminals and housing. All indoor use. Rear Terminal Connections Part Output Out 2/ Option Number 1 Alm 1 2 TEC80001 Relay None None TEC80002 Relay Relay None TEC80003 Relay Relay Relay TEC80004 Pulse DC None None TEC80005 Pulse DC Relay None TEC80006 Pulse DC Relay Relay TEC80007 4-20mA None None TEC80008 4-20mA Relay Relay Stock and Common Part Numbers (Default Type "J" Thermocouple Input)