Temperature Controllers www.tempco.com | (800) 323-6859 | email: [email protected] 13-23 Power Input Standard: 90-250 VAC, 47-63 Hz, 10 VA, 5W maximum Optional: 11-26 VAC / VDC, 10 VA, 5W maximum Signal Input Resolution: 18 bits Sampling Rate: 5 samples / second Accuracy: ±.24% of span typical Maximum Rating: -2 VDC minimum, 12 VDC maximum (1 minute for mA input) Temperature Effect: ±1.5 μV / °C for all inputs except mA input ±3.0 μV / °C for mA input Sensor Lead Resistance Effect: T/C: 0.2μV/ohm 3-wire RTD: 2.6°C/ohm of resistance difference of two leads Burn-out Current: 200nA Common Mode Rejection Ratio (CMRR): 120 dB Normal Mode Rejection Ratio (NMRR): 55 dB Sensor Break Detection: Sensor open for TC, RTD and mV inputs; sensor short for RTD input; below 1 mA for 4-20 mA input; below 0.25V for 1-5V input; unavailable for other inputs Sensor Break Response Time: Within 4 seconds for TC, RTD and mV inputs; 0.1 second for 4-20 mA and 1-5 V inputs Output 1 / Output 2 Relay Rating: 240 VAC, 2 Amp Pulsed Voltage: Source voltage 5V, Current limiting resistance 66Ω Linear Output — Characteristics Type Zero Span Tolerance Tolerance Capacity Load 4-20 mA 3.6-4.0 mA 20-21 mA 500Ω max 0-20 mA 0 mA 20-21 mA 500Ω max 0-5 VDC 0 VDC 5-5.25 VDC 10 KΩ min 1-5 VDC 0.9-1.0 VDC 5-5.25 VDC 10 KΩ min 0-10 VDC 0 VDC 10-10.5 VDC 10 KΩ min Resolution: 15 bit analog to digital converter Output Regulation: 0.02% for full load change Output Settling Time: 0.1 sec. (stable to 99.9%) Isolation Breakdown Voltage: 1000 VAC Temperature Effect: ±0.01 % of span/°C Solid State Relay (Triac) Output Rating: 1A / 240 VAC Inrush Current: 20A for 1 cycle Min. Load Current: 50 mA rms Max. Off-state Leakage: 3 mA rms Max. On-state Voltage: 1.5 VAC rms Insulation Resistance: 1000 Megohms minimum at 500 VDC Dielectric Strength: 2500 VAC for 1 minute Output 2 / Alarm 1 — Programmable Alarm 1 Relay: Form A, (NO) Maximum rating: 240 VAC, 2 Amp Alarm Functions: Dwell timer Deviation High / Low Alarm Deviation Band High / Low Alarm Process High / Low Alarm Sensor Break Alarm Alarm Mode: Normal, Latching, Hold, Latching / Hold Dwell Timer: 0 - 4553.6 minutes Interface: RS-485 (up to 247 units) Protocol: Modbus Protocol – RTU mode Address: 1-247 Baud Rate: 0.3 - 38.4 Kbits/sec Data Bits: 7 or 8 bits Parity Bit: None, Even or Odd Stop Bit: 1 or 2 bits Communication Buffer: 160 bytes User lnterface Single 4-digit LED Displays: 0.4” / 10 mm Keypad: 4 keys Programming Port: For automatic setup, calibration and testing Control Mode Output 1: Reverse (heating) or direct (cooling) action Output 2: PID cooling control, cooling P band 50-300% of PB, dead band -36.0 to 36.0% of PB On-Off: 0.1 - 90.0°F hysteresis control (P band = 0) P or PD: 0 - 100.0% offset adjustment PID: Fuzzy logic modified Proportional band: 0.1 - 900°F Integral time: 0 - 1000 seconds Derivative time: 0 - 360 seconds Cycle Time: 0.1 - 90 seconds Manual Control: Heat (MV1) and Cool (MV2) Auto-tuning: Cold start and warm start Failure Mode: Auto-transfer to manual mode with sensor break or A-D converter damage Ramping Control: 0 - 900°F/min or 0 - 900°F/hr ramp rate Environmental and Physical Operating Temperature: 14 to 122°F (-10 to 50°C) Storage Temperature: -40 to 140°F (-40 to 60°C) Humidity: 0 to 90% RH, non-condensing Dielectric Strength: 2000 VAC, 50/60 Hz for 1 minute Dimensions: 1-7/8 × 1-7/8 × 3-3/4" (48 × 48 × 94 mm) H×W×D Depth behind panel: 3-3/8" (86 mm) Panel Cutout: 1-25/32 × 1-25/32" (45 × 45 mm) H×W Weight: 0.31 lb. (140 grams) Approval Standards Safety: UL61010C-1, EN61010-1 (IEC1010-1) EMC: EN61326 Protective Class: Front Panel: IP30 Housing and Terminals: IP 20 Stock and Common Part Numbers (Power Input: 90-250 VAC) Part Signal Out 2/ Number Input Out 1 Alarm1 TEC15001 tc relay none TEC15002 tc relay relay TEC15003 tc 4-20 mA none TEC15004 tc DC pulse none TEC15005 RTD relay none TEC15006 RTD DC pulse none TEC15007 RTD DC pulse relay Rear Terminal Connections