Temperature Controllers www.tempco.com | (800) 323-6859 | email: [email protected] 13-11 Power Input Standard: 90-250 VAC, 47-63 Hz, 8VA, 4W maximum Optional: 11-40 VDC / 20-8 VAC, 47-63 Hz, 10VA, 5W maximum or 12VA, 6W maximum Signal Input Resolution: 18 Bits Sampling Rate: 5 Times/Sec. (200msec) Maximum Rating: -2VDC minimum, 12VDC maximum Normal Mode Rejection Ratio (NMRR): 55dB Sensor Break Detection: Sensor open for thermocouple and RTD inputs, sensor short for RTD input, below 1mA for 4-20mA input, below 0.25V for 1-5V input, not available for other inputs Sensor Break Responding Time: Within 4 seconds for thermocouple and RTD inputs, 0.1 second for 4-20mA and 1-5V inputs Remote Set Point Input Type: Linear current, Linear voltage Range: -3-27mA, -1.3-11.5V Accuracy: ±0.05 % Input Impedance: Current: 2.5Ω, Voltage:1.5MΩ Resolution: 18 bits Sampling Rate: 1.66 times/second Maximum Rating: 280mA maximum for current input, 12VDC maximum for voltage input Temperature Effect: ±1.5μV / °C for voltage input, ±3.0μV / °C for current input Sensor Break Detection: Below 1mA for 4-20mA input, below 0.25V for 1-5V input, not available for other inputs Event Input No. of Event Inputs: 6 Logic Low: -10Vmin., 0.8V max. Logic High: 2V min., 10V max. CT Input CT Type: TEC99998 Accuracy: ±2% of full scale reading, ± 1 digit max. Input Impedance: 294Ω Measurement Range: 0-50A AC Output of CT: 0-5V DC CT Mount: Wall (Screw) mount Sampling Rate: 1 time/second Output 1 /Output 2 Type: Relay, pulsed voltage, linear voltage and linear current Relay Rating: 2A, 240V AC, 200000 life cycles for resistive load Pulsed Voltage: Source voltage 5V, Current limiting resistance 66Ω Linear Output Resolution: 15 Bits Isolation Breakdown Voltage: 1000 VAC Load Capacity of Linear Output: Linear current: 500Ω maximum, Linear voltage: 10KΩ minimum Alarm Relay Type: Form A Maximum Rating: 2A, 240VAC, 200000 life cycles for resistive load Alarm Functions: Dwell timer, Deviation low, Deviation high, Deviation band low, Deviation band high, Process high, Process low Alarm Mode: Latching, Hold, Normal, Latching/Hold Dwell Timer: 0.1-4553.6 minutes Data Communication Interface: RS-485 Protocol: Modbus RTU Address: 1-247 Baudrate: 2.8-115.2 KBPS Parity Bit: None, Even or Odd Stop Bit: 1 or 2 bits Data Length: 7 or 8 bits Communication Buffer: 160 bytes Analog Retransmission Output signal: 4-20 mA, 0-20 mA, 0-10V Resolution: 15 bits Accuracy: ±0.05% of span ± 0.0025%/°C Load Resistance: 0-500Ω for current output, 10KΩ minimum for voltage output Isolation Breakdown: 1000VAC minimum Integral Linearity Error: ±0.005% of span Linear Output Ranges: 0-2.2mA (0-20mA/4-20mA), 0-5.55V (0-5V, 1-5V), 0-1.1V (0-10V) User Interface Keypad: 4 Keys Display Type: 4 digit LCD display No. of Display: 3 Upper Display Size: 0.7” (17.7mm) Lower Display Size: 0.4” (11.2mm) Programming Port Interface: Micro USB PC Communication Function: Automatic Setup, Calibration and Firmware Upgrade Control Mode Output 1: Reverse (Heating) or Direct (Cooling) Action Output 2: PID cooling control, Cooling P band 50~300% of PB, Dead band -36.0 ~ 36.0 % of PB ON-OFF: 0.1-90.0 (°F ) hysteresis control ( P band = 0) P or PD: 0-100.0 % offset adjustment PID: Fuzzy logic modified Proportional band 0.1 ~ 900.0°F, Integral time 0-3600 seconds, derivative time 0-360.0 seconds Cycle Time: 0.1-90.0 Seconds Manual Control: Heat (MV1) and cool (MV2) Failure Mode: Auto transfer to manual mode while sensor break or A-D Converter damage Ramping Control: 0-900.0°F/Minute or 0-900.0°F/Hour Ramp Rate Profiler Availability: Option No. of Segments/ Program: 4 / 8 / 16 Environmental and Physical Specifications Operating Temp.: -10°C to 50°C Storage Temp: -40°C to 60°C Humidity: 0 to 90 % RH (Non-condensing) Insulation Resistance: 20MΩ minimum (@500V DC) Dielectric Strength: 2000V AC, 50/60 Hz for 1 minute Vibration Resistance: 10-55 Hz, 10m/s2 for 2 hours Shock Resistance: 200 m/s2 (20g) Moldings: Flame retardant polycarbonate Mounting: Panel TEC-8400 TEC-8450 Dimensions H×W×D: 3-3/4 × 1-7/8 × 2-3/8" 1-7/8 × 3-3/4 × 2-3/8" (96 × 48 × 59 mm) (48 × 96 × 59 mm) Depth Behind Panel: 2" (50 mm) 2" (50 mm) Panel Cutout: 1-25/32 × 3-5/8" 3-5/8 × 1-25/32" (45 × 92 mm) (92 × 45 mm) Weight: 8 oz (220 g) 8 oz (220 g) IP50 for the front panel, IP20 for rear terminals and housing. All indoor use. Stock and Common Part Numbers (8400) (Default Type "J" Thermocouple Input) Part Output Out 2/ Alarm Number 1 Alm 1 2 & 3 TEC36001 Relay None None TEC36002 Relay Relay None TEC36003 Relay Relay (2) Relays TEC36004 Pulse DC None None TEC36005 Pulse DC Relay None TEC36006 Pulse DC Relay (2) Relays TEC36007 4-20mA None None TEC36008 4-20mA Relay (2) Relays Note: All Stock Part Numbers Include Terminal Covers Part Output Out 2/ Option Number 1 Alm 1 1 TEC37001 Relay None None TEC37002 Relay Relay None TEC37003 Relay Relay (2) Relays TEC37004 Pulse DC None None TEC37005 Pulse DC Relay None TEC37006 Pulse DC Relay (2) Relays TEC37007 4-20mA None None TEC37008 4-20mA Relay Stock and Common Part Numbers (8450) (Default Type "J" Thermocouple Input) (2) Relays